N2 - Air quality of underground railway is of critical interests in Seoul, Korea. National government has emphasized the stringent management of IAQ of metro-subway. In order to satisfy the legislative standard and public needs, air purification must be much more enhanced with the addition of high quality control facilities. Thus, this work focused on the review of cost effectiveness for replacing fine dust filters. The inflow amount of PM10 and PM2.5 into the test ventilation chamber in which deals with the air, 900 CMM, was 19.4 kg/yr and 8.9 kg/yr respectively. It corresponds to US $ 5,857 for PM 10 and US $ 6,608 for PM2.5 based on the environmental cost evaluation. The current filtration system collects approximately 55% of the inlet PM10 and 35% of PM2.5. Even if it obeys the National IAQ regulation for platforms and ticket rooms, civic groups strongly insist better quality of air inside. Thus, additional facilities to improve the air filtration up to 80% of PM10 and 55% of PM2.5 would cost US$ 8,756 per year. In the future, however, the increase of environmental benefit on the atmospheric dust will in part compensate the cost.
AB - Air quality of underground railway is of critical interests in Seoul, Korea. National government has emphasized the stringent management of IAQ of metro-subway. In order to satisfy the legislative standard and public needs, air purification must be much more enhanced with the addition of high quality control facilities. Thus, this work focused on the review of cost effectiveness for replacing fine dust filters. The inflow amount of PM10 and PM2.5 into the test ventilation chamber in which deals with the air, 900 CMM, was 19.4 kg/yr and 8.9 kg/yr respectively. It corresponds to US $ 5,857 for PM 10 and US $ 6,608 for PM2.5 based on the environmental cost evaluation. The current filtration system collects approximately 55% of the inlet PM10 and 35% of PM2.5. Even if it obeys the National IAQ regulation for platforms and ticket rooms, civic groups strongly insist better quality of air inside. Thus, additional facilities to improve the air filtration up to 80% of PM10 and 55% of PM2.5 would cost US$ 8,756 per year. In the future, however, the increase of environmental benefit on the atmospheric dust will in part compensate the cost.
KW - Air ventilation
KW - Electret filter
KW - Filtration
KW - PM
KW - cost-benefit
UR - https://www.scopus.com/pages/publications/84863076020
M3 - Conference contribution
AN - SCOPUS:84863076020
SN - 9781457708350
T3 - International Conference on Control, Automation and Systems
SP - 309
EP - 314
BT - ICCAS 2011 - 2011 11th International Conference on Control, Automation and Systems
T2 - 2011 11th International Conference on Control, Automation and Systems, ICCAS 2011
Y2 - 26 October 2011 through 29 October 2011
ER -